Minimum and Maximum Heating Cable Lengths:

An all-in-one reference

(Part of our collection of articles on Everything You Need to Know about Heating Cable)

The maximum length of heating cable that you can run with the confidence that you won't blow a fuse depends on several things. Specifically, you need to know:

  • What kind of cable you have: Self-regulating or constant-wattage? What supply voltage? And in some cases, what wire gauge? If you have the full model number, you're set to go.
  • If it's self-regulating, what will be the minimum temperature of the cable when it's started up? (Self-regulating cables draw more power the colder they are, so a cable that runs fine at 50°F might blow your circuit breaker if you start it up at 0°F.)
  • How many amps is your circuit breaker built for?

The most surefire way of making sure you're running a safe length of cable is to check the specific spec sheet for the kind of cable you have; if you ever need them, these spec sheets are available on the ordering pages for each variety of heating cable we sell. However, we've also put together this page as an easy, all-in-one reference for minimum and maximum circuit lengths. Just find the table below that corresponds to the kind of heater you have.

Quick jump to: Self-regulating cable (Low-temperature, Mid-temperature, Freezstop 12/24-volt), Constant-wattage

SELF-REGULATING HEATING CABLE
Series Circuit
breaker
size (amps)
Minimum
circuit
length (ft)
Maximum circuit length (ft), if
start-up temperature is...
50°F
(10°C)
0°F
(–18°C)
–20°F
(–29°C)
Low-temperature styles
SLCAB3120:
3 W/ft
120 VAC
15 1 300 200 180
20 270 230
30 330 330
SLCAB3240:
3 W/ft
240 VAC
15 1 660 410 360
20 560 480
30 660 660
SLCAB5120:
5 W/ft
120 VAC
15 1 230 150 130
20 270 200 175
30 270 260
SLCAB5240:
5 W/ft
240 VAC
15 1 460 300 260
20 540 400 345
30 540 520
SLCAB8120:
8 W/ft
120 VAC
15 1 150 95 85
20 200 125 100
30 210 190 170
40 210 210
SLCAB8240:
8 W/ft
240 VAC
15 1 295 195 170
20 390 250 225
30 420 375 340
40 420 420
SLCAB10120:
10 W/ft
120 VAC
15 1 115 70 60
20 150 95 85
30 180 145 120
40 180 165
SLCAB10240:
10 W/ft
240 VAC
15 1 230 150 130
20 305 200 175
30 360 300 260
40 360 360
Mid-temperature styles
SLMCAB5120:
5 W/ft
120 VAC
15 1 150 135 130
20 200 180 170
30 240 220 210
SLMCAB5240:
5 W/ft
240 VAC
15 1 250 230 220
20 330 305 295
30 480 440 120
SLMCAB10120:
5 W/ft
120 VAC
15 1 30 85 80
20 120 110 105
30 180 165 160
SLMCAB10240:
10 W/ft
240 VAC
15 1 140 130 125
20 190 175 170
30 280 260 250
SLMCAB15120:
15 W/ft
120 VAC
15 1 70 65 60
20 90 85 20
30 130 125 120
SLMCAB15240:
15 W/ft
240 VAC
15 1 100 95 90
20 135 125 120
30 200 185 180

Low-voltage (Freezstop)
Series Circuit
breaker
size (amps)
Minimum
circuit
length (ft)
Maximum circuit length (ft), if
start-up temperature is...
41°F
(5°C)
32°F
(–0°C)
–4°F
(–20°C)
–40°F
(–40°C)
12FLV1:
3.6 W/ft
11/12 VAC
6 1 13 13 9.5 6.5
10 23 19 16 13
16 33 33 26 19
12FLV2:
3.6 W/ft
22/24 VAC
6 1 26 26 19 13
10 46 39 33 26
16 65 65 52 39
17FLV1:
5.2 W/ft
11/12 VAC
6 1 9.5 9.5 9.5 6.5
10 16 16 13 13
16 26 26 23 19
17FLV2:
5.2 W/ft
22/24 VAC
6 1 19 19 19 13
10 33 33 26 26
16 52 52 46 39


CONSTANT-WATTAGE CABLES
Minimum,* maximum circuit length, in feet
*This is found by doubling the circuit module length. When cutting heating cable, we use a minimum length of double the circuit module length to ensure that the cable contains at least one full module.
General-purpose
(note: the model number suffixes -B and -SS can be ignored.)
120 VAC 208 VAC 240 VAC 277 VAC 480 VAC
3 W/ft FECAB3120:
4.0, 360
FECAB3208:
8.0, 625
FECAB3240:
8.0, 720
N/A FECAB3480:
16.0, 1440
5 W/ft FECAB5120:
4.0, 275
FECAB5208:
8.0, 477
FECAB5240:
8.0, 550
N/A FECAB5480:
12.0, 1100
8 W/ft FECAB8120:
4.0, 220
FECAB8208:
8.0, 381
FECAB8240:
8.0, 440
FECAB8277:
8.0, 508
FECAB8480:
12.0, 880
12 W/ft FECAB12120:
4.0, 180
FECAB12208:
12.0, 312
FECAB12240:
4.0, 360
FECAB12277:
8.0, 416
FECAB12480:
8.0, 720
Harsh-environment high-temperature
4 W/ft KECAB4120:
8.0, 310
KECAB4208:
8.0, 537
KECAB4240:
8.0, 620
KECAB4277:
8.0, 716
KECAB4480:
16.0, 1240
8 W/ft KECAB8120:
8.0, 220
KECAB8208:
8.0, 381
KECAB8240:
8.0, 440
KECAB8277:
8.0, 508
KECAB8480:
12.0, 880
12 W/ft KECAB12120:
4.0, 180
KECAB12208:
12.0, 312
KECAB12240:
8.0, 360
KECAB12277:
8.0, 416
KECAB12480:
12.0, 720
Fiberglass high-temperature
(note bus wire size, in American wire gauge)
4 W/ft,
16 AWG
KMCAB412016:
8.0, 190
KMCAB420816:
8.0, 329
KMCAB424016:
8.0, 380
KMCAB427716:
8.0, 439
KMCAB448016:
16.0, 760
4 W/ft,
12 AWG
KMCAB412012:
8.0, 310
KMCAB420812:
8.0, 537
KMCAB424012:
8.0, 620
KMCAB427712:
8.0, 716
KMCAB448012:
16.0, 1240
8 W/ft,
16 AWG
KMCAB812016:
8.0, 112
KMCAB820816:
8.0, 194
KMCAB824016:
8.0, 224
KMCAB827716:
8.0, 259
KMCAB848016:
12.0, 448
8 W/ft,
12 AWG
KMCAB812012:
8.0, 220
KMCAB820812:
8.0, 381
KMCAB824012:
8.0, 440
KMCAB827712:
8.0, 508
KMCAB848012:
12.0, 880
12 W/ft,
12 AWG
KMCAB1212012:
8.0, 180
KMCAB1220812:
12.0, 312
KMCAB1224012:
8.0, 360
KMCAB1227712:
8.0, 416
KMCAB1248012:
8.0, 720
Polyimide high-temperature
4 W/ft KKCAB4120:
8.0, 310
KKCAB4208:
8.0, 537
KKCAB4240:
8.0, 620
KKCAB4277:
8.0, 716
KKCAB4480:
16.0, 1240
8 W/ft KKCAB8120:
4.0, 220
KKCAB8208:
8.0, 381
KKCAB8240:
8.0, 440
KKCAB8277:
8.0, 508
KKCAB8480:
12.0, 880
12 W/ft KKCAB12120:
4.0, 180
KKCAB12208:
8.0, 312
KKCAB12240:
8.0, 360
KKCAB12277:
8.0, 416
KKCAB12480:
14.0, 720
18 W/ft KKCAB18120:
3.5, 120
KKCAB18208:
6.0, 208
KKCAB18240:
7.0, 240
KKCAB18277:
8.0, 277
KKCAB18480:
11.0, 480